ECP49354T-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1785RPM, L449T Frame UPC #781568690550

ECP49354T-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1785RPM, L449T Frame UPC #781568690550

ECP50358LR-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 895RPM, 5012 Frame UPC #781568834862

ECP50358LR-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 895RPM, 5012 Frame UPC #781568834862

ECP50356LR-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1194RPM, 5010 Frame UPC #781568825532

Part #ECP50356LR-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1194RPM, 5010 Frame.
Special Price $84,310.53 was $94,465.58
SKU
ECP50356LR-4-781568825532
ECP50356LR-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1194RPM, 5010 Frame UPC #781568825532 is available to buy in increments of 1

Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1194RPM, 5010 Frame

Features

  • Robust cast iron construction
  • Regreasable bearings all frames
  • IP55, IP54 on 5000 frame and larger
  • Embossed raised letter, 304 stainless steel nameplates
  • Inverter ready nameplate
  • Division 2, Class I, Groups A,B,C,D markings on nameplate

Applications

  • Chemical, Oil & Gas
  • Pulp & Paper, Forest Products
  • Metals & Foundries
  • Cement, Aggregate & above ground Mining
  • Food Processing
  • Power Generation

Specification

Output 350 hp      KVA Code H
Phase 3 Motor Lead Quantity/Wire Size 9 @ 1 AWG
Synchronous Speed 1200 rpm Motor Lead Termination Flying Leads
Frequency 60 Hz Motor Standards NEMA
Voltage 460 V Motor Type A50212M
Frame Material Iron Number of Poles 6
Frame 5010 Power Factor 84
XP Class and Group NONE Product Family General Industrial
XP Division Division II Pulley End Bearing Type Roller
Brand Baldor-Reliance Pulley Face Code Standard
Agency Approvals CCSA US Pulley Shaft Indicator Standard
Ambient Temperature 40 °C Service Factor 1.15
Bearing Grease Type POLYREX EM (-20F +300F) Shaft Extension Location Pulley End
Current 405.0 A Shaft Ground Indicator Shaft Grounding
Duty Rating CONT Shaft Rotation Reversible
Efficiency @ 100% Load 95.8% Shaft Slinger Indicator Shaft Slinger
Electrically Isolated Bearing Electrically Isolated Bearings Speed 1194 rpm
Feedback Device No feedback Speed Code Single Speed
Front Face Code Standard Starting Method Direct on line
Front Shaft Indicator None Thermal Device - Bearing None
Heater Indicator Heater Included, 120 V Thermal Device - Winding RTD Only
High Voltage Full Load Amps 405.0 A Sensor No Vibration Sensor
Insulation Class F XP Temp Code T3C
Inverter Code Not inverter

 

NamePlate

ENERGY EFFICIENT   SERIAL NO.  
CAT.NO. ECP50356LR-4 SPEC NO. KECP50356LR-4A
HP 350 AMPS 1194 FRAME 27CG5010Y HZ 60 SERVICE FACTOR 1.15
VOLTS 460 F.L. AMPS 405 PHASE 3 TYPE   ENCL. TEFC
NEMA NOM. EFF 95.8 F.L.P.F. 84 MOTOR WEIGHT 5000 INSUL.CLASS F
DESIGN  - NEMA CODE H MAX AMBIENT 40 DUTY CONT
  C RISE/ 115 AT   HP 403 AMPS 462
D.E. BRG. 120RU03M30X26 O.D.E. BRG. 110BC02J30X
WDG. THERMAL 100 OHM PLATINUM QTY. 6   BRG. THERMAL  
LUBE POLYREX EM  
 VOLTS 120 AMPS  2.0 WATTS 236 QTY 4
CERTIFICATE OF COMP NO. LR53258, CC010A

                                                                                      000613007QB

 

T. CODE T3C
CL I DIV 2 GR C & D CL II DIV 2 GR
MOTOR I.D. NO.  

                               000692000UY

 

Part Number Description Quantity List Price
034017014AB LCKW 3/8 STD. PLATED 4.000 EA 4.00 USD
034017014AB LCKW 3/8 STD. PLATED 4.000 EA 4.00 USD
034017014AB LCKW 3/8 STD. PLATED 4.000 EA 4.00 USD
034017012AB LCKW 1/4 STD. PLATED 4.000 EA 2.00 USD
034017014AB LCKW 3/8 STD. PLATED 4.000 EA 4.00 USD
032130006AB HSHCS 1/4-20X3/4L PLTD. 2.000 EA 5.00 USD



***Please Note: Item Photos above are for General Reference and may not always be exact. Please see the product description and quick overview section for complete listing of item details and any additional components and specifications***

More Information
Product Availability Ships within 24 to 48 hours
Manufacturer Baldor
Output 350 hp
Speed 1200 rpm
Phase Three Phase
Frequency 60 Hz
Frame 5010
Motor Type A50212M
Efficiencies @ 100% Load 95.8%
High Voltage Full Load Amps (FLA) 397 A
Service Factor 1.15
Number of Poles 6
Motor Voltage 460V
Write Your Own Review
You're reviewing:ECP50356LR-4 Baldor Three Phase, Totally Enclosed, Foot Mounted 350HP, 1194RPM, 5010 Frame UPC #781568825532
More from Baldor